C02 絶 縁 電 線 IV の 許 容 電 流 y-326 | ||||||||||
導体径 | 許容電流 (A) (電流減少係数含む) | |||||||||
形状 | IV電線を同一管、線ぴ、ダクト内に収める場合の電線数 | |||||||||
単線 | 撚線 | 碍子引き | VV3C以下 | 3本以下 | 4本 | 5~6 | 7~15 | 16~40 | 41~60 | 61本以上 |
1.2 | (19) | (13) | (13) | (12) | (10) | (9) | (8) | (7) | (6) | |
1.6 | 27 | 19 | 19 | 17 | 15 | 13 | 12 | 11 | 9 | |
2.0 | 35 | 24 | 24 | 22 | 19 | 17 | 15 | 14 | 12 | |
2.6 | 48 | 33 | 33 | 30 | 27 | 23 | 21 | 19 | 17 | |
3.2 | 62 | 43 | 43 | 38 | 34 | 30 | 27 | 24 | 21 | |
0.9 | (17) | (11) | (11) | (10) | (9) | (8) | (7) | (6) | (5) | |
1.25 | (19) | (13) | (13) | (11) | (10) | (9) | (8) | (7) | (6) | |
2 | 27 | 18 | 18 | 17 | 15 | 13 | 11 | 10 | 9 | |
3.5 | 37 | 26 | 26 | 23 | 20 | 18 | 16 | 14 | 12 | |
5.5 | 49 | 34 | 34 | 31 | 27 | 24 | 21 | 19 | 16 | |
8 | 61 | 42 | 42 | 38 | 34 | 30 | 26 | 24 | 21 | |
14 | 88 | 61 | 61 | 55 | 49 | 43 | 38 | 34 | 30 | |
22 | 115 | 80 | 80 | 72 | 64 | 56 | 49 | 45 | 39 | |
38 | 162 | 113 | 113 | 102 | 90 | 79 | 70 | 63 | 55 | |
60 | 217 | 150 | 152 | 136 | 121 | 106 | 93 | 85 | 74 | |
100 | 298 | 202 | 208 | 187 | 167 | 146 | 128 | 116 | 101 | |
150 | 395 | 269 | 276 | 249 | 221 | 193 | 170 | 154 | 134 | |
200 | 469 | 318 | 328 | 295 | 262 | 230 | 202 | 183 | 159 | |
250 | 556 | 367 | 389 | 350 | 311 | 272 | 239 | 217 | 189 | |
325 | 650 | 435 | 455 | 409 | 364 | 318 | 280 | 254 | 221 | |
400 | 745 | - | 521 | 469 | 417 | 365 | 320 | 291 | 253 | |
500 | 842 | - | 589 | 530 | 471 | 412 | 328 | 328 | 286 | |
電流減少係数 | 0.70 | 0.63 | 0.56 | 0.49 | 0.43 | 0.39 | 0.34 |
電流減少係数(内規1340-2表) 絶縁電線を合成樹脂線ぴ、合成樹脂管、金属線ピ、金属管、可とう電線管に収めて 使用する場合に適用する。 |
備考
周囲温度が30℃以外の場合は、下表の電流補正係数を乗じて許容電流値を補正する。
周囲温度 ℃ | 20 | 25 | 35 | 40 | 45 | 50 |
電流補正係数 | 1.25 | 1.08 | 0.91 | 0.82 | 0.71 | 0.58 |